Language
Negotiable
The date of payment from buyers deliver within days
Beijing
Long-term effective
2017-11-08 12:45
113
eastsolar(Ms.)
Beijing
1418 Lexington Street, Tustin, California, United States
Model | Model 200 | Model 300 | Model 400 | Model 500 | Model 600 |
Rated max capacity | 200kVA | 300kVA | 400kVA | 500kVA | 600kVA |
Numbers of power modules | 4 | 6 | 8 | 10 | 12 |
Rated capacity of power module | 50kVA | ||||
Input | |||||
Input wiring | 3Ph + N + PE | ||||
Rated voltage | 380/400/415V AC | ||||
Voltage range | 138-485V AC (305-485V AC without power downgrading, 138-305V AC with linear downgrading 40%) | ||||
Input frequency | 40-70Hz | ||||
Power factor | ≥ 0.99 | ||||
Harmonic current distortion | < 3% THDi | ||||
Batteries | |||||
Type | VRLA/AGM maintenance-free lead based | ||||
Battery voltage | ± 240V DC (± 180/192/204/216/228/252/264/276V DC selectable) | ||||
Number of battery | 40 pieces (30/32/34/36/38/42/44/46 pieces selectable) | ||||
Max charging current | 10A x quantity of configured power modules (settable) | ||||
Output | |||||
Output wiring | 3Ph + N + PE | ||||
Rated voltage | 380/400/415V AC | ||||
Voltage accuracy | ± 1% | ||||
Frequency | mains mode: synchronized with utility battery mode: 50/60Hz ± 0.25% |
||||
Power factor | 0.9 | ||||
Voltage distortion | ≤ 1% with liner load/ ≤ 3% with non-linear load | ||||
Dynamic variation | ± 5% | ||||
Transient recovery time | < 20 minutes | ||||
Crest factor | 3:1 | ||||
Inverter overload capacity | 105-110% for 60 minutes, 110-125% for 10 minutes 125-150% for 1 minute, > 150% for 200 minutes |
||||
Bypass overload capacity | Load ≤ 135% for long term running: 135% < load <1000% for 100 minutes | ||||
System | |||||
Efficiency | 96 % | ||||
Max number of parallel | 4 units | ||||
Transfer time | 0 minute | ||||
Protections | Short-circuit, overload, over-temperature, overvoltage, under voltage, battery low voltage, output low/over voltage and fans failure | ||||
Communications | RS485, dry contacts, FE port (SNMP) | ||||
Display | 7 inches LCD touchscreen | ||||
Others | |||||
Operating temperature | 0 to 40°C | ||||
Storage temperature | - 40 to 70°C | ||||
Humidity | 0-95% (non-condensing) | ||||
Altitude | 0-4000m Above 1000m, derating 1% for each additional 100m |
||||
IP rating | IP 20 | ||||
Noise level at 1 m | <65dB | <68dB | |||
Cabinet dimensions | (W) 600 x (D) 850 x (H) 2000mm | (W) 1200 x (D) 850 x (H) 2000mm | (W) 1400 x (D) 850 x (H) 2000mm | ||
UPS module dimensions | (W) 442 x (D) 620 x (H) 130mm | ||||
Cabinet weight | 213kg | 426kg | 426kg | 448kg | 568kg |
UPS module weight | 32kg |